Product Description
The single-phase distribution transformer is small in size and light in weight, allowing it to be installed deep within load centers, shortening the radius of the low-voltage network and reducing energy losses.
Product Features
- When the power supply radius of a three-phase distribution transformer is too large, the load density is low, and the voltage at the end of power lines drops, affecting normal user electricity, installing a single-phase distribution transformer at the end of the power supply line can shorten the low-voltage power supply radius and solve the problem of low user voltage.
- When a three-phase distribution transformer is overloaded, a single-phase distribution transformer can be installed on an appropriate branch line based on load characteristics to transfer load and solve the problem of capacity increase.
- Installing a single-phase distribution transformer in residential areas with no three-phase electricity demand will shorten the low-voltage power supply radius and reduce losses.
- Installing a single-phase distribution transformer in areas with low load density, wide distribution, and no three-phase electricity can reduce investment and solve the problem of long-distance power supply.
Installation Method
According to user requirements, we can provide a pole-mounted installation structure, which is convenient for installation and reduces material costs for substation areas.
Technical Parameters
| Rated Capacity(kVA) | Rated Voltage(kV) | Short-circuit Impedance(%) | ConnectionSymbol | No-Load Losses(W) | Load Losses(W) | No-Load Current(%) |
|
| HV | LV |
|
|
|
|
|
| 5 | 6 / 6.3 / 10 / 10.5 / 11 | 2×(0.22–0.24) or 0.22–0.24 | 3.5 | II0 / II6 | 28 | 130 | 4.0 |
| 10 |
|
|
|
| 44 | 234 | 3.5 |
| 16 |
|
|
|
| 52 | 328 | 3.2 |
| 20 |
|
|
|
| 64 | 387 | 3.0 |
| 30 |
|
|
|
| 80 | 500 | 2.8 |
| 40 |
|
|
|
| 100 | 698 | 2.5 |
| 50 |
|
|
|
| 120 | 855 | 2.3 |
| 63 |
|
|
|
| 144 | 1022 | 2.1 |
| 80 |
|
|
|
| 160 | 1260 | 2.0 |
| 100 |
|
|
|
| 192 | 1485 | 1.9 |
| 125 |
|
|
|
| 228 | 1755 | 1.8 |
| 160 |
|
|
|
| 2130 | 2130 | 1.7 |
Notes:
- The performance parameters of other capacity products shall be determined through consultation between the manufacturer and the user.
- For combination transformers with low voltage of 2×(0.22–0.24) kV, when the low voltage is (0.22–0.24) kV, the capacity is reduced by 50% (except for parallel operation).
- For short-circuit impedance and short-circuit current, they shall be determined after consultation between the manufacturer and the user.